38 MONITOR ISM™/AFx™ IP Connectivity Guide 22-9058 v2.1
5) IP board receiving data, but not
responding (red LED is not pulsing).
The data being received may not be
configured correctly for the panel (such
as incorrect panel serial number
).
6) IP Board Receiving Data and
Responding (red LED is pulsing in
sync with the green LED) but, still no
communications.
This may mean the
"Remote IP Address" and "Remote
Port" are being used, but have been set
incorrectly. Try disabling this feature
(zero-out these values), and then re-try
communications. If successful, re-
enable this feature using the correct
values (see
4.3.2 for details).
7) NOTE: When an IP Interface Module
is powered for the first time, the
board’s green DIR RX and SIP RX
LED’s will flash alternately to indicate
the board is not
programmed. These
same lights flash on and off together
at the same time when the board is
in
Discovery Mode and ready to be
programmed.
Comentarios a estos manuales